HEAT PUMP BASICS

This course assumes that you are already proficient in the operation of comfort cooling. The cooling function of a heat pump is identical to that of a straight air conditioner with the exception that the refrigerant flows through the reversing valve and accumulator (if one is present). All the power circuitry is identical and all the components are the same. Some of the earliest experiments with refrigeration were done by Lord Kelvin in 1852 See article in Wikipedia on Lord Kelvin a.k.a William Thomson. Note: there is an article on Wikipedia on heat pumps which has some serious errors because there is no mention of Latent Heat, only gas laws which relate the pressure of a gas with temperature not the change in state of the refrigerant from liquid to gas and back..

A heat pump is an air conditioner that can be reversed to move heat from outside to inside. In some countries a heat pump is also known as a "reverse cycle air conditioner". In most cases heat pumps are air to air but there are systems that use air and fluid or fluid and fluid. A Ground source or Geothermal heat pump uses fluid that passes through the earth to transfer the heat energy instead of the air but will be almost identical in function.

Without getting into a major physics discussion at this time, the fact is that a comfort cooling system will move more heat from the evaporator to the condenser than the amount of electrical energy supplied to the compressor. The heat that is discharged from the condenser is the latent heat that is picked up from the evaporator plus the motor heat from the compressor. For comparison it is practical to get a 3 to 1 return on the energy input to the compressor. Even today as a rule of thumb for comfort cooling 1 electrical horsepower equals 12,000 BTUs/hr (1 Ton ) of energy moved. So a compressor motor which is rated at 1HP (746 Watts) which is close to 3,000 Btus/hr (2536.4 to be exact)  Btus/hr will move 12,000 Btus/hr  or a 4 to 1 return.

 If the cost of electricity is 10 cents a kWh, to produce heat with straight resistance heat will be 100,000 (1 Therm) divided by 3,400 Btus or $2.94 a Therm. Using $3.00 a therm divided by a COP. of 3 a heat pump will cost $1 a Therm to operate all things being equal, which makes it very competitive will all forms of energy including coal and wood. To get the base cost per therm of electricity take the base at 10 cents a kWh and multiply it times your rate in cents per kWh divided by 10 (8 cents a kWh= $3.00 a Therm times .8 ).

For space heating purposes it is possible to to move enough heat to satisfy the load at typical Winter conditions such as 30F outdoor and 70F indoor conditions if the system is properly sized for Summer  cooling load.

The closer the temperature between the evaporator and condenser and the larger either coil the more heat is transfered
for a given time and compressor capacity. If either coil is reduced in size and the temperature difference is increased then the amount of heat transfered is reduced for a given time and compressor capacity.

The major advantage of a ground source heat pump over an air to air is that the temperatures of the ground fluid are closer to the indoor temperature or in the case of cooling may be below the indoor temperature resulting in extreme efficiencies.

Some buildings have loop systems where heat pumps are placed throughout the building and in cooling mode the loop water is fed to a cooling tower or ground loop and in heating mode sourced from a boiler.


Copyright © 2007 Scott Meenen
All rights reserved